Wire Size Calculator (with MCB size)

Enter your load and cable length; it picks the copper wire size and the MCB that protects it, and checks the voltage drop.

How the wire size is chosen

The current is worked out from the load (a 1.5 ton AC is taken as about 1,600 W). Geysers, heaters, ACs and pumps on single phase get at least 2.5 sq mm wire and a 16 A MCB, as they sit on a 16 A power point; three-phase motors get at least 1.5 sq mm. The MCB is the next standard size above the current, with extra room for motors and ACs that draw more when starting. The wire must carry at least the MCB rating, so the MCB protects the wire, and the voltage drop over the cable length must stay within the limit; if it does not, the next bigger wire is chosen.

Wire (copper, sq mm)Typical current in conduitCommon use
1.0about 10 ALights, fans (6 A MCB)
1.5about 13 ALights, fans, 6 A sockets (6-10 A MCB)
2.5about 18 A16 A sockets, geyser, 1-1.5 ton AC (16 A MCB)
4.0about 24 A2 ton AC, kitchen power line (20 A MCB)
6.0about 31 AMain line of a small house (25-32 A MCB)
10about 42 AMain line, large loads (40 A MCB)

Figures are typical values for PVC / FR copper house wire run in conduit or casing; open runs carry a little more, bunched cables less. Always follow the wire maker's chart and get wiring done by a licensed electrician.